NEC Ampacity Data
Download PDF
Email PDF
Table 310.15(B)(2)(b) Ambient Temperature Correction Factors Based on 40°C (104°F)
For ambient temperatures other than 40°C (104°F), multiply the allowable ampacities specified in the ampacity tables by the appropriate correction factor shown below.
Temperature Rating of Conductor | |||||||
Ambient Temperature (°C) | 60°C | 75°C | 90°C | 150°C | 200°C | 250°C | Ambient Temperature (°F) |
10 or less | 1.58 | 1.36 | 1.26 | 1.13 | 1.09 | 1.07 | 50 or less |
11-15 | 1.50 | 1.31 | 1.22 | 1.11 | 1.08 | 1.06 | 51-59 |
16-20 | 1.41 | 1.25 | 1.18 | 1.09 | 1.06 | 1.05 | 60-68 |
21-25 | 1.32 | 1.20 | 1.14 | 1.07 | 1.05 | 1.04 | 69-77 |
26-30 | 1.22 | 1.13 | 1.10 | 1.04 | 1.03 | 1.02 | 78-86 |
31-35 | 1.12 | 1.07 | 1.05 | 1.02 | 1.02 | 1.01 | 87-95 |
36-40 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 96-104 |
41-45 | 0.87 | 0.93 | 0.95 | 0.98 | 0.98 | 0.99 | 105-113 |
46-50 | 0.71 | 0.85 | 0.89 | 0.95 | 0.97 | 0.98 | 114-122 |
51-55 | 0.50 | 0.76 | 0.84 | 0.93 | 0.95 | 0.96 | 123-131 |
56-60 | – | 0.65 | 0.77 | 0.90 | 0.94 | 0.95 | 132-140 |
61-65 | – | 0.53 | 0.71 | 0.88 | 0.92 | 0.94 | 141-149 |
66-70 | – | 0.38 | 0.63 | 0.85 | 0.90 | 0.93 | 150-158 |
71-75 | – | – | 0.55 | 0.83 | 0.88 | 0.91 | 159-167 |
76-80 | – | – | 0.45 | 0.80 | 0.87 | 0.90 | 168-176 |
81-90 | – | – | – | 0.74 | 0.83 | 0.87 | 177-194 |
91-100 | – | – | – | 0.67 | 0.79 | 0.85 | 195-212 |
101-110 | – | – | – | 0.60 | 0.75 | 0.82 | 213-230 |
111-120 | – | – | – | 0.52 | 0.71 | 0.79 | 231-248 |
121-130 | – | – | – | 0.43 | 0.66 | 0.76 | 249-266 |
131-140 | – | – | – | 0.30 | 0.61 | 0.72 | 267-284 |
141-160 | – | – | – | – | 0.50 | 0.65 | 285-320 |
161-180 | – | – | – | – | 0.35 | 0.58 | 321-356 |
181-200 | – | – | – | – | – | 0.49 | 357-392 |
201-225 | – | – | – | – | – | 0.35 | 393-437 |
Table 310.15(B)(3)(a) Adjustment Factors for More Than Three Current-Carrying Conductors in a Raceway or Cable
Number of Conductors | Percent of Values in Table 310.15(B)(16) through Table 310.15(B)(19) as Adjusted for Ambient Temperature if Necessary |
4-6 | 80 |
7-9 | 70 |
10-20 | 50 |
21-30 | 45 |
31-40 | 40 |
41 and above | 35 |
* Number of conductors is the total number of conductors in the raceway or cable adjusted in accordance with 31 0.15(B)(5) and (6).
Informational Note No. 2: See 366.23(A) for adjustment factors for conductors in sheet metal auxiliary gutters and 376.22(B) for adjustment factors for conductors in metal wireways.
(1) Where conductors are installed in cable trays, the provisions of 392.80 shall apply.
(2) Adjustment factors shall not apply to conductors in raceways having a length not exceeding 600 mm (24 in.).
(3) Adjustment factors shall not apply to underground conductors
entering or leaving an outdoor trench if those conductors have
physical protection in the form of rigid metal conduit, intermediate
metal conduit, rigid polyvinyl chloride conduit (PVC), or reinforced
thermosetting resin conduit (RTRC) having a length not exceeding 3.05 m
(10 ft), and if the number of conductors does not exceed four.
(4) Adjustment factors shall not apply to Type AC cable or to Type MC cable under the following conditions:
- The cables do not have an overall outer jacket.
- Each cable has not more than three current-carrying conductors.
- The conductors are 12 AWG copper.
- Not more than 20 current-carrying conductors are installed without maintaining spacing, are stacked, or are supported on”bridle rings.”
(5) An adjustment factor of 60 percent shall be applied to Type AC cable or Type MC cable under the following conditions:
- The cables do not have an overall outer jacket.
- The number of current carrying conductors exceeds 20.
- The cables are stacked or bundled longer that 600 mm (24 in) without spacing being maintained.
(b) More Than One Conduit, Tube, or Raceway. Spacing between conduits, tubing, or raceways shall be maintained.
(c) Circular Raceways Exposed to Sunlight on Rooftops. Where
conductors or cables are installed in circular raceways exposed to
direct sunlight on or above rooftops, the adjustments shown in Table
310.15(B)(3)(c) shall be added to the outdoor temperature to determine
the applicable ambient temperature for application of the correction
factors in Table 31 0.15(B)(2)(a) or Table 31 0.15(B)(2)(b).
Informational Note: One source for the average ambient temperatures in various locations is the ASHRAE Handbook – Fundamentals.
Table 310.15(B)(3)(c) Ambient Temperature Adjustment for Circular Raceways Exposed to Sunlight on or Above Rooftops
Distance Above Roof to Bottom of Conduit | Temperature Adder °C | Temperature Adder °F |
0-13 mm (½ in.) | 33 | 60 |
Above 13 mm (½ in.) – 90 mm (3½ in.) | 22 | 40 |
Above 90 mm (3½ in.) – 300 mm (12 in.) | 17 | 30 |
Above 300 mm (12 in.) – 900 mm (36 in.) | 14 | 25 |
Informational Note to Table 31 0.15(B)(3)(c): The temperature adders in Table 310.15(B)(3)(c) are based on the results of averaging the ambient temperatures.
(4) Bare or Covered Conductors. Where bare or covered conductors are installed with insulated conductors, the temperature rating of the bare or covered conductor shall be equal to the lowest temperature rating of the insulated conductors for the purpose of determining ampacity.
(5) Neutral Conductor.
(a) A neutral conductor that carries only the unbalanced
current from other conductors of the same circuit shall not be required
to be counted when applying the provisions of 310.15(B)(3)(a).
(b) In a 3-wire circuit consisting of two phase conductors and the
neutral conductor of a 4-wire, 3-phase, wye-connected system, a common
conductor carries approximately the same current as the line-to-neutral
load currents of the other conductors and shall be counted when
applying the provisions of 310.15(B)(3)(a).
(c) On a 4-wire, 3-phase wye circuit where the major portion of the load
consists of nonlinear loads, harmonic currents are present in the
neutral conductor; the neutral conductor shall therefore be considered a
current-carrying conductor.
(6) Grounding or Bonding Conductor. A grounding or bonding conductor shall not be counted when applying the provisions of 31 0.15(B)(3)(a).
Table 310.15(B)(16) (formerly Table 310.16) Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)*
Temperature Rating of Conductor [See Table 310.104(A).] | |||||||
60°C (140°F) | 75°C (167°F) | 90°C (194°F) | 60°C (140°F) | 75°C (167°F) | 90°C (194°F) | ||
Types TW, UF | Types RHW, THHW, THW, THWN, XHHW, USE, ZW | Types TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN·2, USE-2, XHH, XHHW, XHHW-2, ZW-2 | Types TW, UF | Types RHW, THHW, THW, THWN, XHHW, USE | Types TBS, SA, SIS, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2 | ||
Size AWG or kcmil | COPPER | ALUMINUM OR COPPER-CLAD ALUMINUM | Size AWG or kcmil | ||||
18 | – | – | 14 | – | – | – | – |
16 | – | – | 18 | – | – | – | – |
14** | 15 | 20 | 25 | – | – | – | – |
12** | 20 | 25 | 30 | 15 | 20 | 25 | 12** |
10** | 30 | 35 | 40 | 25 | 30 | 35 | 10** |
8 | 40 | 50 | 55 | 35 | 40 | 45 | 8 |
6 | 55 | 65 | 75 | 40 | 50 | 55 | 6 |
4 | 70 | 85 | 95 | 55 | 65 | 75 | 4 |
3 | 85 | 100 | 115 | 65 | 75 | 85 | 3 |
2 | 95 | 115 | 130 | 75 | 90 | 100 | 2 |
1 | 110 | 130 | 145 | 85 | 100 | 115 | 1 |
1/0 | 125 | 150 | 170 | 100 | 120 | 135 | 1/0 |
2/0 | 145 | 175 | 195 | 115 | 135 | 150 | 2/0 |
3/0 | 165 | 200 | 225 | 130 | 155 | 175 | 3/0 |
4/0 | 195 | 230 | 260 | 150 | 180 | 205 | 4/0 |
250 | 215 | 255 | 290 | 170 | 205 | 230 | 250 |
300 | 240 | 285 | 320 | 195 | 230 | 260 | 300 |
350 | 260 | 310 | 350 | 210 | 250 | 280 | 350 |
400 | 280 | 335 | 380 | 225 | 270 | 305 | 400 |
500 | 320 | 380 | 430 | 260 | 310 | 350 | 500 |
600 | 350 | 420 | 475 | 285 | 340 | 385 | 600 |
700 | 385 | 460 | 520 | 315 | 375 | 425 | 700 |
750 | 400 | 475 | 535 | 320 | 385 | 435 | 750 |
800 | 410 | 490 | 555 | 330 | 395 | 445 | 800 |
900 | 435 | 520 | 585 | 355 | 425 | 480 | 900 |
1000 | 455 | 545 | 615 | 375 | 445 | 500 | 1000 |
1250 | 495 | 590 | 665 | 405 | 485 | 545 | 1250 |
1500 | 525 | 625 | 705 | 435 | 520 | 585 | 1500 |
1750 | 545 | 650 | 735 | 455 | 545 | 615 | 1750 |
2000 | 555 | 665 | 750 | 470 | 560 | 630 | 2000 |
*Refer to 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other than 30°C (86°F).
**Refer to 240.4(D) for conductor overcurrent protection limitations.
Table 310.15(B)(17) (formerly Table 310.17) Allowable Ampacities of Single-Insulated Conductors Rated Up to and Including 2000 Volts in Free Air, Based on Ambient Temperature of 30°C (86°F)*
Temperature Rating of Conductor [See Table 310.104(A).] | |||||||
60°C (140°F) | 75°C (167°F) | 90°C (194°F) | 60°C (140°F) | 75°C (167°F) | 90°C (194°F) | ||
Types TW, UF | Types RHW, THHW, THW, THWN, XHHW, ZW | Types TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN·2, USE-2, XHH, XHHW, XHHW-2, ZW-2 | Types TW, UF | Types RHW, THHW, THW, THWN, XHHW | Types TBS, SA, SIS, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2 | ||
Size AWG or kcmil | COPPER | ALUMINUM OR COPPER-CLAD ALUMINUM | Size AWG or kcmil | ||||
18 | – | – | 18 | – | – | – | – |
16 | – | – | 24 | – | – | – | – |
14** | 25 | 30 | 35 | – | – | – | – |
12** | 30 | 35 | 40 | 25 | 30 | 35 | 12** |
10** | 40 | 50 | 55 | 35 | 40 | 45 | 10** |
8 | 60 | 70 | 80 | 45 | 55 | 60 | 8 |
6 | 80 | 95 | 105 | 60 | 75 | 85 | 6 |
4 | 105 | 125 | 140 | 80 | 100 | 115 | 4 |
3 | 120 | 145 | 165 | 95 | 115 | 130 | 3 |
2 | 140 | 170 | 190 | 110 | 135 | 150 | 2 |
1 | 165 | 195 | 220 | 130 | 155 | 175 | 1 |
1/0 | 195 | 230 | 260 | 150 | 180 | 205 | 1/0 |
2/0 | 225 | 265 | 300 | 175 | 210 | 235 | 2/0 |
3/0 | 260 | 310 | 350 | 200 | 240 | 270 | 3/0 |
4/0 | 300 | 360 | 405 | 235 | 280 | 315 | 4/0 |
250 | 340 | 405 | 455 | 265 | 315 | 355 | 250 |
300 | 375 | 445 | 500 | 290 | 350 | 395 | 300 |
350 | 420 | 505 | 570 | 330 | 395 | 445 | 350 |
400 | 455 | 545 | 615 | 355 | 425 | 480 | 400 |
500 | 515 | 620 | 700 | 405 | 485 | 545 | 500 |
600 | 575 | 690 | 780 | 455 | 545 | 615 | 600 |
700 | 630 | 755 | 850 | 500 | 595 | 670 | 700 |
750 | 655 | 785 | 885 | 515 | 620 | 700 | 750 |
800 | 680 | 815 | 920 | 535 | 645 | 725 | 800 |
900 | 730 | 870 | 980 | 580 | 700 | 790 | 900 |
1000 | 780 | 935 | 1055 | 625 | 750 | 845 | 1000 |
1250 | 890 | 1065 | 1200 | 710 | 855 | 965 | 1250 |
1500 | 980 | 1175 | 1325 | 795 | 950 | 1070 | 1500 |
1750 | 1070 | 1280 | 1445 | 875 | 1050 | 1185 | 1750 |
2000 | 1155 | 1385 | 1560 | 960 | 1150 | 1295 | 2000 |
*Refer to 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other than 30°C (86°F).
**Refer to 240.4(D) for conductor overcurrent protection limitations.
Table 310.15(B)(20) (formerly Table 310.20) Ampacities of Not More Than Three Single Insulated Conductors, Rated Up to and Including 2000 Volts, Supported on a Messenger, Based on Ambient Air Temperature of 40°C (104°F)
Temperature Rating of Conductor [See Table 310.104(A).] | |||||
75°C (167°F) | 90°C (194°F) | 75°C (167°F) | 90°C (194°F) | ||
Types RHW, THHW, THW, THWN, XHHW, ZW | Types MI, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHHW, XHHW-2, ZW-2 | Types RHW, THW, THWN, THHW, XHHW | Types THHN, THHW, RHH, XHHW, RHW-2, XHHW-2, THW-2, THWN-2, USE-2, ZW-2 | ||
Size AWG or kcmil | COPPER | ALUMINUM OR COPPER-CLAD ALUMINUM | Size AWG or kcmil | ||
8 | 57 | 66 | 44 | 51 | 8 |
6 | 76 | 89 | 59 | 69 | 6 |
4 | 101 | 117 | 78 | 91 | 4 |
3 | 118 | 138 | 92 | 107 | 3 |
2 | 135 | 158 | 106 | 123 | 2 |
1 | 158 | 185 | 123 | 144 | 1 |
1/0 | 183 | 214 | 143 | 167 | 1/0 |
2/0 | 212 | 247 | 165 | 193 | 2/0 |
3/0 | 245 | 287 | 192 | 224 | 3/0 |
4/0 | 287 | 335 | 224 | 262 | 4/0 |
250 | 320 | 374 | 251 | 292 | 250 |
300 | 359 | 419 | 282 | 328 | 300 |
350 | 397 | 464 | 312 | 364 | 350 |
400 | 430 | 503 | 339 | 395 | 400 |
500 | 496 | 580 | 392 | 458 | 500 |
600 | 553 | 647 | 440 | 514 | 600 |
700 | 610 | 714 | 488 | 570 | 700 |
750 | 638 | 747 | 512 | 598 | 750 |
800 | 660 | 773 | 532 | 622 | 800 |
900 | 704 | 826 | 572 | 669 | 900 |
1000 | 748 | 879 | 612 | 716 | 1000 |
*Refer to 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other than 40°C (104°F).
Table 310.15(B)(21) (formerly Table 310.21) Ampacities of Bare or Covered Conductors in Free Air, Based on 40°C (104°F) Ambient, 80°C (176°F) Total Conductor Temperature, 610 mm/sec (2 ft/sec) Wind Velocity
Copper Conductors | AAC Aluminum Conductors | ||||||
Bare | Covered | Bare | Covered | ||||
AWG or kcmil | Amperes | AWG or kcmil | Amperes | AWG or kcmil | Amperes | AWG or kcmil | Amperes |
8 | 98 | 8 | 103 | 8 | 76 | 8 | 80 |
6 | 124 | 6 | 130 | 6 | 96 | 6 | 101 |
4 | 155 | 4 | 163 | 4 | 121 | 4 | 127 |
2 | 209 | 2 | 219 | 2 | 163 | 2 | 171 |
1/0 | 282 | 1/0 | 297 | 1/0 | 220 | 1/0 | 231 |
2/0 | 329 | 2/0 | 344 | 2/0 | 255 | 2/0 | 268 |
3/0 | 382 | 3/0 | 401 | 3/0 | 297 | 3/0 | 312 |
4/0 | 444 | 4/0 | 466 | 4/0 | 346 | 4/0 | 364 |
250 | 494 | 250 | 519 | 266.8 | 403 | 266.8 | 423 |
300 | 556 | 300 | 584 | 336.4 | 468 | 336.4 | 492 |
500 | 773 | 500 | 812 | 397.5 | 522 | 397.5 | 548 |
750 | 1000 | 750 | 1050 | 477 | 588 | 477 | 617 |
1000 | 1193 | 1000 | 1253 | 556.5 | 650 | 556.5 | 682 |
– | – | – | – | 636 | 709 | 636 | 744 |
– | – | – | – | 795 | 819 | 795 | 860 |
– | – | – | – | 954 | 920 | – | – |
– | – | – | – | 1033.5 | 968 | 1033.5 | 1017 |
– | – | – | – | 1272 | 1103 | 1272 | 1201 |
– | – | – | – | 1590 | 1267 | 1590 | 1381 |
– | – | – | – | 2000 | 1454 | 2000 | 1527 |
Table 310.60(C)(4) Ambient Temperature Correction Factors
For ambient temperatures other than 40°C (104°F), multiply the allowable ampacities specified in the ampacity tables by the appropriate factor shown below.
Temperature Rating of Conductor | |||
Ambient Temperature (°C) | 90°C | 105°C | Ambient Temperature (°F) |
10 or less | 1.26 | 1.21 | 50 or less |
11-15 | 1.22 | 1.18 | 51-59 |
16-20 | 1.18 | 1.14 | 60-68 |
21-25 | 1.14 | 1.11 | 69-77 |
26-30 | 1.10 | 1.07 | 78-86 |
31-35 | 1.05 | 1.04 | 87-95 |
36-40 | 1.00 | 1.00 | 96-104 |
41-45 | 0.95 | 0.96 | 105-113 |
46-50 | 0.89 | 0.92 | 114-122 |
51-55 | 0.84 | 0.88 | 123-131 |
56-60 | 0.77 | 0.83 | 132-140 |
61-65 | 0.71 | 0.78 | 141-149 |
66-70 | 0.63 | 0.73 | 150-158 |
71-75 | 0.55 | 0.68 | 159-167 |
76-80 | 0.45 | 0.62 | 168-176 |
81-85 | 0.32 | 0.55 | 177-185 |
86-90 | – | 0.48 | 186-194 |
91-95 | – | 0.39 | 195-203 |
96-100 | – | 0.28 | 204-212 |
Table 310.60(C)(67) Ampacities of Insulated Single Copper Conductor Cables Triplexed in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)*
Temperature Rating of Conductor [See Table 310.104(C).] | ||||
2001-5000 Volts Ampacity | 5001-35,000 Volts Ampacity | |||
Conductor Size (AWG or kcmil) | 90°C (194°F) Type MV-90 | 105°C (221°F) Type MV-105 | 90°C (194°F) Type MV-90 | 105°C (221°F) Type MV-105 |
8 | 65 | 74 | – | – |
6 | 90 | 99 | 100 | 110 |
4 | 120 | 130 | 130 | 140 |
2 | 160 | 175 | 170 | 195 |
1 | 185 | 205 | 195 | 225 |
1/0 | 215 | 240 | 225 | 255 |
2/0 | 250 | 275 | 260 | 295 |
3/0 | 290 | 320 | 300 | 340 |
4/0 | 335 | 375 | 345 | 390 |
250 | 375 | 415 | 380 | 430 |
350 | 465 | 515 | 470 | 525 |
500 | 580 | 645 | 580 | 650 |
750 | 750 | 835 | 730 | 820 |
1000 | 880 | 980 | 850 | 950 |
*Refer to 310.60(C)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F).
Table 310.60(C)(68) Ampacities of Insulated Single Aluminum Conductor Cables Triplexed in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)*
Temperature Rating of Conductor [See Table 310.104(C).] | ||||
2001-5000 Volts Ampacity | 5001-35,000 Volts Ampacity | |||
Conductor Size (AWG or kcmil) | 90°C (194°F) Type MV-90 | 105°C (221°F) Type MV-105 | 90°C (194°F) Type MV-90 | 105°C (221°F) Type MV-105 |
8 | 50 | 57 | – | – |
6 | 70 | 77 | 75 | 84 |
4 | 90 | 100 | 100 | 110 |
2 | 125 | 135 | 130 | 150 |
1 | 145 | 160 | 150 | 175 |
1/0 | 170 | 185 | 175 | 200 |
2/0 | 195 | 215 | 200 | 230 |
3/0 | 225 | 250 | 230 | 265 |
4/0 | 265 | 290 | 270 | 305 |
250 | 295 | 325 | 300 | 335 |
350 | 365 | 405 | 370 | 415 |
500 | 460 | 510 | 460 | 515 |
750 | 600 | 665 | 590 | 660 |
1000 | 715 | 800 | 700 | 780 |
*Refer to 310.60(C)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F).
Table 310.60(C)(69) Ampacities of Insulated Single Copper Conductor Isolated in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)*
Temperature Rating of Conductor [See Table 310.104(C).] | ||||||
2001-5000 Volts Ampacity | 5001-15,000 Volts Ampacity | 15,001-35,000 Volts Ampacity | ||||
Conductor Size (AWG or kcmil) | 90°C (194°F) Type MV-90 | 105°C (221°F) Type MV-105 | 90°C (194°F) Type MV-90 | 105°C (221°F) Type MV-105 | 90°C (194°F) Type MV-90 | 105°C (221°F) Type MV-105 |
8 | 83 | 93 | – | – | – | – |
6 | 110 | 120 | 110 | 125 | – | – |
4 | 145 | 160 | 150 | 165 | – | – |
2 | 190 | 215 | 195 | 215 | – | – |
1 | 225 | 250 | 225 | 250 | 225 | 250 |
1/0 | 260 | 290 | 260 | 290 | 260 | 290 |
2/0 | 300 | 330 | 300 | 335 | 300 | 330 |
3/0 | 345 | 385 | 345 | 385 | 345 | 380 |
4/0 | 400 | 445 | 400 | 445 | 395 | 445 |
250 | 445 | 495 | 445 | 495 | 440 | 490 |
350 | 550 | 615 | 550 | 610 | 545 | 605 |
500 | 695 | 775 | 685 | 765 | 680 | 755 |
750 | 900 | 1000 | 885 | 990 | 870 | 970 |
1000 | 1075 | 1200 | 1060 | 1185 | 1040 | 1160 |
1250 | 1230 | 1370 | 1210 | 1350 | 1185 | 1320 |
1500 | 1365 | 1525 | 1345 | 1500 | 1315 | 1465 |
1750 | 1495 | 1665 | 1470 | 1640 | 1430 | 1595 |
2000 | 1605 | 1790 | 1575 | 1755 | 1535 | 1710 |
*Refer to 310.60(C)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F).